SINGLE DETECTOR ON A ZONE CONNECTION
If a zone has only one detector all the EOLRs and a jumper must be installed on this detectors board (see figures 11 and 11a):
· 2.7K (Red-Gray-Red) EOLR must be installed between contacts 1 & 2
· 5.6K (Green-Blue-Red) EOLR must be installed between contacts 4 & 5
· 10K (Brown-Black-Orange) EOLR must be installed between contacts 7 & 8
· Jumper must connect contacts 4 & 7.
Detector is connected to the UltraGuard Monitor with 4 wires (Figure 11a).