POWER CONNECTION
From the selected 12V power source strip the insulation back ¼ on the two conductor power cord. Connect the (12VDC) power
to the two-position plug (J1) (figure 21 below) of the input 12VDC only. The UltraGuard 12V may also be powered by an
alternate power source (Such as the Altronix AL300ULX, configured for 12VDC operation. The installation of the Altronix
AL300ULX must be in accordance with the AL300ULX installation manual.
CAUTION: Connect the 12VDC correctly to the (+) and (-) terminals.
FINAL INSTALLATION
Insert each of the CO Detector plugs on the Zone connector strip being sure to press in place firmly. The shoulder of the plug
should be flush against the top of the connector. DO NOT connect the alarm panel wiring until all CO Detectors are connected
and operating properly.
CAUTION: Before continuing to the configuration mode, connect power (12VDC) to J1. Press the self-test button
on each Detector to verify that each of the installed CO Detectors is powered and functioning. If a Detector fails,
correct the problem before processing. Never use the configuration mode unless all Detectors are operating correctly.
CONFIGURATION
CAUTION: DO NOT attempt configuration until all the wires for the CO Detectors in all zones you use are connected
to the UltraGuard 12V electronic board! If the CO Detectors are not so connected or if they are wired incorrectly
the UltraGuard 12V will go into the INOPERABLE mode (see troubleshooting below).
Refer to figure 21 below. BEFORE applying power, place jumper J7 in the Config. Position.
When power is applied (12VDC) to J1, UltraGuard 12V
determines the system configuration and stores that information.
It will then respond with three rapid beeps, flash the power,
trouble and the replace CO Detector LEDs and flash the Zone
LEDs for the zones with CO Detectors attached. The UltraGuard
12V will continue to beep and flash the LEDs about twice a
second until the Config jumper is placed in the Normal
position. Placing the jumper in the Normal position will
return the UltraGuard 12V to normal operation.
Insert each of the alarm panel plugs on the alarm connector
strip being sure to press in place firmly. The shoulder of the
plug should be flush against the top of the connector.
NOTE: The BASIC mode requires only a single alarm panel
plug. Unused alarm contacts are left open. If the BASIC alarm
panel being used has a fault/trouble input, the Any Fault
output connector may be used.
In a case of power loss the UltraGuard 12V Monitor will re-
establish the system configuration when the power is restored.
Troubleshooting:
If the unit goes into the INOPERABLE mode due to an incorrect configuration procedure the following will happen:
1. Power, Trouble and Replace Detector lights flash every second with no pattern.
2. UltraGuard Monitor emits a beeping noise.
3. Reset Button does not eliminate the condition.
Check if the zones are connected to the UltraGuard 12V and all the detectors are wired/functioning properly.
Repeat the configuration sequence as described in this section.