EVO Control Panel 13
4.8 EOL on Hardwire Zones
SECTION [3033]: OPTION [7]
(default = disabled) If detection devices connected to hardwired input
terminals use 1k
Ω end of line resistors, enable option [7] in section [3033].
For details on using EOL resistors, refer to Addressable Zone Connections
on page 5 and Double Zone Connections on page 6.
4.9 Keypad Numbering
SECTIONS [2801] TO [2832]
Keypad Numbering identifies the keypad in the event buffer. The keypad is
assigned to a Keypad Number from 1 to 32 through the keypad's serial
number in sections [2801] to [2832].