10 REFERENCE & INSTALLATION MANUAL
2.13 FIRE CIRCUITS
When a zone is program med as a Fire zone, the zone becomes normally open and
requi res an EOL resistor. If a line shor t occurs or if the sm oke detector becomes
active, whether the system is armed or disarmed, the control panel will generate an
alarm. If a trouble occurs on a Fire zone, the Fire Loop Trouble will appear in the
keypads’ Trouble Display (see page 46) and the control panel can transmit the Fire
Loop Trouble report, if programmed, in section [206].
2.13.1 4-WIR E INSTALLA TION:
Any on-board zone can be defined as a Fire Zone (see page 18) when
using the 4-wir e installation. C onnect the smoke detectors as show n in
Figure 2.9 directly to the control panel terminals. Program the PGM with the
“[PG ]/[FNC1] Key was Pressed” Activation Event (see page 37) so the
smoke detectors can be reset by pressing the [PG ] or [FN C 1] key. Pressing
the [PG] or [FNC1] key will interrupt power to the smoke detectors for 4
seconds (see PGM Delay on page 38).
It is recommended that all 4-wire smoke detectors be connected using a daisy chain configuration.
PART 3: PROGRAMMING METHODS
3.1 WINLOAD SOFTWARE FOR WINDOWS
Program the Spectra Series control panels remotely or on-site using the Winload Software for Windows®. For more
information, contact your local Paradox Distributor or visit our web site at http://www.paradox.ca. If you are using the
WinLoad software, you must program the features explained on pages 44 and 45.
3.2 PROGRAMMING USING A KEYPAD
Use the supplied Sp ectra 1728EX, 1728, 173 8EX and 1 738 Prog ramm ing Guide to keep track of which sections
were programmed and how. We recommend you read this entire manual before you begin pr ogramming.
3.2.1 SINGLE DIGIT DATA ENTRY MET HO D (HEXADEC IMA L AND DECIMAL)
Si ngle Digit D ata Entry is used in all sections except those specified in the Fea tur e Select Prog rammi ng
Method. After entering the programming mode as described in the shaded box above, some sections will
require that you enter Decimal values from 000 to 255. Other sections will require that you enter
Hexadecimal values from 0 to F. The required data wi ll be clearly indicated i n this manual as well as i n the
Spectra 1728EX, 1728, 1738EX and 1738 Programming Guide. When entering the final digit in a section,
the control panel will automatically save and advance to the next section. Except sections 001 to 016, after
entering the first two digits the control panel wil l switch to Feature Select Programming.
How Do I Enter Programming Mode?
STEP 1: Press [ENTER]
STEP 2: Enter your [INSTALLER COD E] (default: 000000 or 0000)
STEP 3: Enter 3-digit [SECTION] you wish to program
STEP 4: Enter required [DATA]
Figure 2.9: Fire Z ones