SPECTRA SERIES 27
7.3 TAMPER RECOGNITION
Section [1 32 ]: Zone Option s
[1] OFF / [2] OF F: Tamp er R ecogn ition Disab led (defau lt)
If the system is armed or disarmed
, the control panel will display the zone as open in the keypad display, but will
not generate an alarm. This option is not permitted on UL systems.
[1] OFF / [2] ON : Trouble Only
If the system is armed
and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Al arm
Types setting (see page 21).
If t he sy stem is disarme d
and a tamper wiring failure occurs on a zone, a Tamper/
Zone Wiring Failure will appear in the keypads Trouble Display (see page 46) and the control panel will transmit the
appropriate Zone Tamper report code (see page 31).
[1] ON / [2] OF F: Sile nt Alar m
If the system is armed
and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Al arm
Types setting (see page 21). In a disarmed system, it functions the same as the Trouble Only setting, but it will also
generate a silent alarm. A silent alarm will not trigger any bells or sirens, but the system will have to be disarmed.
[1] ON / [2] ON : Audible Alarm
In an a rme d sy st em and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Al arm
Types setting (see page 21). In a disa rmed syst em, it functions the same as Trouble Only setting, except it will also
generate an audible alarm.
7.3.1 TAM PER BYP AS S OPTIONS
Section [132]: Zone Options
Option [3] OFF = Will generate a tamper if detected on a bypassed zone (default)
Option [3] ON = Tampers on bypassed zones will be ignored
With option [3] on, the Tamper Recognition feature follows the zone bypass definition. This means the
control panel will ignore any tampers detected on a bypassed zone. With option [3] off, Tamper
Recognition ignores the bypass definition. This means the control panel will generate an incident as per
Tamper Recognition settings if a tamper or wire fault occurs on a bypassed zone.
7.4 KEYPAD PANIC OPTIONS
Section [128 ]: General Op tion s
Option [1] OFF = Emergency Panic Disabled (default)
Option [1] ON = Emergency Panic Enabled
Pressing the [1] and [3] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as
defined by option [4].
Option [2] OFF = Auxiliary Panic Disabled (default)
Option [2] ON = Auxiliary Panic Enabled
Pressing the [4] and [6] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as
defined by option [5].
Option [3] OFF = Fire Panic Disabled (default)
Option [3] ON = Fire Pani c Enabled
Pressing the [7] and [9] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as
defined by option [6].
Option [4] OFF = Emergency Panic is Silent (default)
Option [4] ON = Emergency Panic is Audi ble
Option [5] OFF = Auxiliary Panic is Silent (default)
Option [5] ON = Auxiliary Panic is Audible
Option [6] OFF = Fire Panic is Silent (default)
Option [6] ON = Fire Panic i s Pulsed