44 REFERENCE & INSTALLATION MANUAL
Step 3: If more than one Trouble Group appears, highlight the desired
group before pressing the center action key (View) to view the
specific trouble.
If Access Control is enabled in the system and the option Door
Access during Clock Loss is
ON (section [3038] option [8]), only the
System Master Code and User Codes with the Master feature
enabled will be able to program the clock. Enter the System Master
or a Master Code, press [
TRBL], then continue with the steps above.
15.13 TROUBLE LATCH
S
ECTION [3033]: OPTION [6]
With the Trouble Latch feature disabled, when a trouble occurs and is
corrected, the trouble is automatically cleared and no longer displayed.
With the Trouble Latch feature enabled, the trouble will remain displayed
until it is manually cleared by the user. To clear the trouble, the user must
enter the trouble display (see section 15.12) and then exit the trouble
display. For LCD and LED keypads, press [
CLEAR] to exit. For Grafica
keypads, press the left action key (Back) to exit.
Only troubles that have been corrected can be cleared. If a
trouble has not been corrected, it will continue to be displayed
even if the user tries to clear the trouble by using the method
described above.
15.14 CLEAR BELL CURRENT LIMIT TROUBLE
S
ECTION [3030]: OPTION [7]
(Default: OFF) When an activated bell output is shorted, a Bell Current Limit
trouble is displayed and can be sent to the Central Station. This feature
determines how the Bell Current Limit trouble is cleared.
UL Note: For UL installations, section [3030] option [7] must be
enabled (ON).
Only troubles that have been corrected can be cleared. If a
trouble has not been corrected, it will continue to be displayed
even if the user tries to clear the trouble through the trouble
display.
Trouble Description
GROUP [1]: SYSTEM
[1] AC Failure
Power failure detected. The system is
running on the backup battery.
[2] Battery Trouble
The backup battery is disconnected, needs
to be recharged or replaced.
[3] AUX Current Limit
Devices connected to AUX have exceeded
current limits (1.1A). The Auxiliary Output
will shutdown until the trouble is corrected.
[4] Bell Current Limit
The bell or siren has exceeded current
limits (3A). The Bell/Siren Output will
shutdown until the trouble is corrected.
[5] Bell Absent
The bell or siren is not connected. When
the bell output is not used, connect a 1k
resistor across the bell output.
[6] ROM Check Error
The control panel registers a data memory
error. Contact distributor for replacement.
[7] RAM Check Error
The control panel registers a work memory
error. Contact distributor for replacement.
GROUP [2]: COMMUNICATOR
[1] TLM1
The control panel is unable to access the
main telephone line.
[2] Fail to Communicate 1
[3] Fail to Communicate 2
[4] Fail to Communicate 3
[5] Fail to Communicate 4
The control panel tried all assigned
telephone numbers and failed to contact
the Monitoring Company.
[6] Fail to Communicate PC
The control panel is unable to
communicate with the WinLoad software.
GROUP [3]: MODULES
[1] Module Tamper A module’s tamper switch was triggered
[2] ROM Check Error
A module is experiencing a data memory
error. Contact distributor for replacement.
[3] TLM Trouble
A module is unable to access the
telephone line.
[4] Fail to Communicate
A module failed to communicate with the
Monitoring Company.
[5] Printer Trouble
The control panel registers a problem with
a printer connected to a Printer Module.
Check printer for problems (paper jam, no
paper, no power, etc.).
[6] AC Failure Module power failure.
[7] Battery Failure Module's battery is disconnected, needs to
be recharged or needs to be replaced.
[8] Supply Output Module has exceeded current limits.
GROUP [4]: NETWORK (COMBUS)
[1] Missing Keypad
A keypad is no longer communicating with
the control panel.
[2] Missing Module
A device is no longer communicating with
the control panel.
[3] General Failure
No communication between the devices
and the control panel.
[4] Combus Overload
Too many devices (over 127) are on the
combus.
GROUP [5]: ZONE TAMPER
Press [5] to display zone(s) Zones displayed were tampered.
GROUP [6]: ZONE LOW BATTERY
Press [6] to display zone(s)
Zone displayed indicates where a wireless
device’s battery needs to be replaced.
Also, the device’s yellow light will flash.
GROUP [7]: ZONE FAULT
Press [7] to display zone(s)
A smoke detector is experiencing a wiring
problem, needs to be cleaned, or a
wireless device is no longer communicating
with its receiver (supervision loss).
GROUP [8]: CLOCK LOSS
Press [8] to re-program
The time and date were reset to default.
Step 1: Press the [8] key
Step 2: Set the hour and minutes according
to the 24-hour clock (i.e. 9AM is
09:00 and 9PM is 21:00).
Step 3: Enter the correct date according to
yyyy/mm/dd.
Step 4: Press [
CLEAR] to exit.
Option Description
[7]
ON
When an activated bell output is shorted, the Bell Current
Limit trouble will remain displayed until it is manually
cleared by the user. The user must clear the trouble
through the trouble display.
[7]
OFF
When an activated bell output is shorted, the DigiplexNE
control panel will attempt to reactivate the bell output once
every minute for as long as the bell is activated. The Bell
Current Limit trouble is cleared automatically the first time
the control panel does not detect a short when attempting
to reactivate the bell.
Trouble Description